Insulator type |
AC normal type |
GB standard No. |
XP-100 |
XP-120 |
XP-125 |
XP-125 |
Fig |
1 |
1 |
1 |
2 |
Specified mechanical load (kN) |
100 |
120 |
125 |
125 |
Class |
U100BL |
U120BS |
U125BS |
U125BL |
Nominal unit spacing (mm) |
146 |
146 |
146 |
178 |
Nominal diameter (mm) |
255/280 |
255 |
255 |
280/292 |
Nominal creepage distance (mm) |
295/340 |
295/320 |
295 |
324/356 |
Ball & socket size |
16 |
16 |
20 |
20 |
Electro mechanical failing load (kN) |
100 |
120 |
125 |
125 |
Mechanical routine test load (kN) |
50 |
60 |
62.5 |
62.5 |
Power frequency withstand voltage |
Dry kV |
70 |
70 |
70 |
70 |
Wet (kV) |
40 |
40 |
40 |
40 |
Lightning impulse withstand voltage (kV) |
100 |
100 |
100 |
100 |
Power frequency puncture voltage (kV) |
110 |
110 |
110 |
110 |
Radio interference voltage |
Test voltage to ground (kV) |
10 |
10 |
10 |
10 |
Max . RIV at 1MHz (μV) |
50 |
50 |
50 |
50 |
Weight (kg) |
5.7/6.1 |
5.7 |
5.8 |
8.0 |
Applicable standard: GB IEC AS BS IS |