Insulator type |
AC anti-pollution type |
GB standard No. |
XHP-80-M |
XHP-80C-M |
XHP-110-M |
Fig |
2 |
1 |
2 |
Specified mechanical load (kN) |
80 |
110 |
ANSI standard No. |
52-3 |
52-4 |
52-5 |
Nominal unit spacing (mm) |
146 |
146 |
146 |
Nominal diameter (mm) |
255 |
255 |
255 |
Minimum creepage distance (mm) |
432 |
432 |
432 |
Combined M&E strength (kN) |
80 |
80 |
111 |
Tension proof test load (kN) |
40 |
40 |
55.5 |
Mechanical impact strength (Nm) |
6 |
6 |
7 |
Low frequency flashover voltage |
Dry kV |
100 |
100 |
100 |
Wet (kV) |
60 |
60 |
60 |
Critical impulse flashover voltage |
Positive (kV) |
150 |
150 |
150 |
Negative (kV) |
160 |
160 |
160 |
Low frequency puncture voltage (kV) |
120 |
120 |
120 |
Radio interference voltage |
Test voltage to ground (kV) |
10 |
10 |
10 |
Max. RIV at 1MHz μV |
50 |
50 |
50 |
Weigh (kg) |
6.2 |
6.2 |
7.7 |
Applicable standard: ANSI C29.2 |