Insulator type |
AC normal type |
GB standard No. |
XP-45C-M |
XP5-70C-M |
XP5-70-M |
XP-70-M |
Fig |
1 |
2 |
3 |
3 |
Specified mechanical load (kN) |
45 |
70 |
ANSI standard No. |
52-1 |
52-2 |
52-2 |
52-3 |
Nominal unit spacing (mm) |
140 |
146 |
146 |
146 |
Nominal diameter (mm) |
160 |
200 |
200 |
225 |
Minimum creepage distance (mm) |
178 |
210 |
210 |
292 |
Combined M&E strength (kN) |
45 |
70 |
70 |
70 |
Tension proof test load (kN) |
22.5 |
35 |
35 |
35 |
Mechanical impact strength (Nm) |
5 |
6 |
6 |
6 |
Low frequency flashover voltage |
Dry kV |
60 |
65 |
65 |
80 |
Wet (kV) |
30 |
35 |
35 |
50 |
Critical impulse flashover voltage |
Positive (kV) |
100 |
115 |
115 |
125 |
Negative (kV) |
100 |
115 |
115 |
130 |
Low frequency puncture voltage (kV) |
80 |
90 |
90 |
110 |
Radio interference voltage |
Test voltage to ground (kV) |
7.5 |
10 |
10 |
10 |
Max. RIV at 1MHz (μV) |
50 |
50 |
50 |
50 |
Weight (kg) |
2.5 |
3.6 |
3.6 |
4.6 |
Applicable standard: ANSI C29.2 |