Insulator type |
AC anti-pollution type |
GB standard No. |
XHP-100 |
XHP1-100 |
XHP2-100 |
XHP3-100 |
Fig |
1 |
1 |
1 |
2 |
Specified mechanical load (kN) |
100 |
Class |
U100BLP |
U100BLP |
U100BLP |
U100BLP |
Nominal unit spacing (mm) |
160 |
146 |
146 |
146 |
Nominal diameter (mm) |
280 |
280 |
255 |
320 |
Nominal creepage distance (mm) |
430 |
450 |
432 |
555 |
Ball & socket size |
16 |
16 |
16 |
16 |
Electro mechanical failing load (kN) |
100 |
100 |
100 |
100 |
Mechanical routine test load (kN) |
50 |
50 |
50 |
50 |
Power frequency withstand voltage |
Dry kV |
80 |
80 |
80 |
80 |
Wet (kV) |
45 |
45 |
42 |
55 |
Lightning impulse withstand voltage (kV) |
120 |
120 |
120 |
120 |
Power frequency puncture voltage (kV) |
120 |
120 |
120 |
120 |
Radio interference voltage |
Test voltage to ground (kV) |
10 |
10 |
10 |
10 |
Max . RIV at 1MHz (μV) |
50 |
50 |
50 |
50 |
Weight (kg) |
7.9 |
7.6 |
7.9 |
11.0 |
Applicable standard: GB IEC AS BS IS |