Pin Insulators For High Voltage Lines

Disc Insulator For High Voltage

Post Insulator For High Voltage Lines

Strain Insulator For Lines

Low Voltage Insulator For Lines

Strain Rod Insulators

Ceramic Bridge Insulator

Pin Insulators For High Voltage Lines
Cat. No. C2222、C2223、C2224、C2225、C2226
National standard: ANSI
Views:
Query Tel: 86-799-7586600
Details
Main dimensions and standard particulars
Cat. No. C2222 C2223 C2224 C2225 C2226
ANSI class 57-11 57-12 57-13 57-14 57-15
Creepage distance (mm)
Dry arcing distance (mm)
356
165
559
241
737
311
1015
368
1145
438
Cantilever strength (kN) 12.5 12.5 12.5 12.5 12.5
Low frequency dry flashover voltage (kV)
Low frequency wet flashover voltage (kV)
Critical impulse flashover, pos (kV)
Critical impulse flashover, neg (kV)
80
60
130
155
110
85
180
205
125
100
210
260
150
125
255
340
175
150
290
380
Test voltage to ground (kV)
Max . RIV at 1MHz (μV)
15
100
22
100
30
200
44
200
44
200
Net weight, each, approx (kg)
Number in standrad package
6.8
6
10
3
11.8
3
15.9
2
18.6
2