Insulator type |
D.C. anti-pollution type |
GB standard No. |
XZP-70 |
XZP-120 |
XZP-160 |
XZP-210 |
XZP-240 |
Specified mechanical load (kN) |
70 |
120 |
160 |
210 |
240 |
Class |
U70BLP |
U120BLP |
U160LP |
U210BSP |
U240BSP |
Nominal unit spacing (mm) |
146 |
146 |
170 |
170 |
170 |
Nominal diameter (mm) |
280 |
280 |
320 |
320 |
320 |
Nominal creepage distance (mm) |
450 |
450 |
545 |
545 |
545 |
Ball & socket size |
16 |
16 |
20 |
20/24 |
24 |
Electro mechanical failing load (kN) |
70 |
120 |
160 |
210 |
210 |
Mechanical routine test load (kN) |
35 |
60 |
80 |
105 |
120 |
D.C. withstand voltage(±) |
Dry kV |
125 |
125 |
140 |
140 |
140 |
Wet (kV) |
50 |
50 |
55 |
55 |
55 |
Dry lightning impulse withstand voltage (kV) |
130 |
130 |
140 |
140 |
140 |
Power frequency puncture voltage(±) |
Dry kV |
140 |
140 |
155 |
155 |
155 |
Wet (kV) |
55 |
55 |
60 |
60 |
60 |
puncture voltage inSF6(+) |
185 |
185 |
210 |
210 |
210 |
Weigh (kg) |
6.7 |
7.7 |
12.8 |
13.8 |
14.1 |
Applicable standard: GB IEC IS |